ENGM029 Power System Analysis Lab Sheet _ Lab 1Python

Java Python ENGM029

Power System Analysis

Lab Sheet Lab 1

Before your Start

•   Ensure you read the instruction document ‘DIgSILENT PowerFactory Modelling Instruction’ and DIgSILENT tutorial documents ‘DIgSILENT Tutorial_Introduction’, ‘DIgSILENT Tutorial_Project’, ‘DIgSILENT Tutorial_LoadFlow’ in the ELE page;

•   DIgSILENT PowerFactory provides Student Licence (PF4S); you are encouraged to make direct contact with DIgSILENT to acquire one licence so you can install in your own computer and can access to and practice the simulation study remotely.

Requirements on Report

•   A report needs to be produced to answer each question in the lab sheet.

•   Assessment: The lab report has a total of 100 marks. The lab report counts for 10% of your final mark.

•   The report should be written in a concise manner to both summarising and discussing the results.

•   The report  should be  submitted as PDF file online through ELE2 system by noon,  1st December 2023.

•  Avoid any form. of plagiarism.

•   Format to be used for the results:

Voltage in p.u.:

3 decimal places

(e.g., 0.965 p.u.)

Voltage in kV:

1 decimal place

(e.g., 132.5 kV)

Power in MW/MVA:

1 decimal place

(e.g., 200.7 MW)

1. Objective

The first Power System Analysis lab aims to enhance your knowledge and skills in power system modelling and power flow calculation and analysis. At the end of the lab session, you should be able to build simple power network model, including generator, transformer, transmission line and load, and carry out power flow simulation and analyse by explaining indicative parameters such as active power, reactive power, bus voltage magnitude and phase angle.

2. Introduction

In this Lab Session, you will learn how to simulate a small power transmission network and  how to perform. power flow calculation in a powerful modern power system simulation software, DIgSILENT PowerFactory. By this simulation exercise, you will learn the underload and  overload effects over a long transmission distance on the system operational performance, mitigation method to stablise the bus voltage, and the efficient Newton-Raphson approach and its application in simulation calculation.

3.  Problem 1 _ Power Flow Problem [50 marks]

Preparation

Open the project file ‘Power System Analysis_Lab  1_P1.pfd’. Ensure the library contains generator type G1, tower type L6, conductor types 1Z×275 kV_ASCR Zebra 400 mm2  and 4Z×275 kV_ASCR Zebra 400 mm2  (300×300).

Problem formation:

A load centre is supplied by hydro-generator (11 kV terminal voltage) through a 11/275 kV step-up transformer, a 200 km long double-circuit transmission line operating at 275 kV, and a 275/33 kV step-down transformer. The configuration of the transmission system is given in the Figure Q1. The load level varies from 40 MW to 340 MW.

Figure Q1

The parameters of the components are given in the following tables:

Transmission Line

Table 1 Double-circuit Transmission Line Parameter

Line length

200 km

Tower Type

L6

Transposition

Perfect (or none)

Conductor Type

4Zx275kV_ASCR Zebra 400mm2 (300x300)

Earth Conductor Type

1Zx275 kV_ASCR Zebra 400mm2

Note: tower, conductor and earth conductor types are included in the library in the project file. Transformer

Table 2. Transformer Parameters

Voltage Ratio

Connection

Power Rating

Short-circuit  impedance %

Load loss kW

No

load

current %

No Load loss kW

Step-up

transformer

T1

1-2

11/275

Yd11

180

MVA

15

450

0.5

60

Step-down transformer

T2

3-4

275/33

YNd11

200

MVA

16

500

0.8

80

Bus

Table 3 Bus Voltage

Bus Number

Voltage Rating kV

Bus 1

11

Bus 2

275

Bus 3

275

Bus 4

33

Generator

Table 4. Generator Parameters

Bus type

G1

Rated Apparent Power

400 MVA

Rated Voltage

11 kV

Rated Power Factor

1.

Note: generator type is included in the library in the project file

Question 1.1: Network conditions with loads at unity power factor [15 marks]

•    Run power flow calculation for loads of 40, 80, 120, 160, 240 and 280 MW

•    Record the active and reactive powers as well as voltage magnitudes and phases of

the generator bus and load bus. Present your recordings in the form. of table/figure in your report;     [10 marks]

•    Discuss your findings;                                                                                       [5 marks]

•    Note:

o To change the setting of active power for the load, go into the ‘power flow’ tab in the load model;

o To run a power flow calculation, click on the ‘Load Flow Calculation’ button

Question 1.2: Network conditions with loads at 0.9 inductive power factor [15 marks]

•    Change the load power factor to 0.9 inductive by introducing appropriate MVAr values

•    Run power flow calculation for loads of 40, 80, 120 and 160 MW. And record the

new active and reactive powers as well as voltage magnitudes and phases of the

generator bus and load bus. Present your recordings in the form. of table/figure in your report;          [10 marks]

•    Discuss your findings and specify the loads at which the voltage drops below 0.9 p.u.; [5  marks]

•    Note:

o To change the setting of reactive power for the load, go into the ‘power flow’ tab in the load model;

Question 1.3: Network conditions with loads at 0.9 inductive power factor with reactive power compensation [20 marks]

•    One approach to keep the load voltage as close to 1.0 p.u. as possible is to connect a source of reactive power near the load bus. In this case, a shunt capacitor or a shunt inductor is added to the load bus. It will produce or absorb reactive power to support and maintain the voltage.

•    Connect a shunt capacitor/inductor model to the load bus and change its rated voltage and adjust the rated reactive power setting. Repeat the calculations in Question 1.2.

•    Find the most suitable values of the reactive power generation/absorption of the shunt capacitor/inductor to maintain the load bus voltage as close as possible to 1.0 p.u. for each load level. And record the reactive power values, new active and reactive powers as well as voltage magnitudes and phases of the generator bus and load bus. Present your recordings in the form. of table/figure in your report;  [15  marks]

•    Discuss your findings;                                                                                       [5 marks]

•    Note:

o To set the reactive power rating, goto the ‘shunt RLC ’ model, choose capacitor or inductor type, and adjust the rated reactive power value

o Keep the number of step in the ‘shunt capacitor’ as 1.

4.  Problem 2 _ N-R Iterative Power Flow Calculation [50 marks]

Preparation

Open the project file ‘Power System Analysis_Lab  1_P2.pfd’. Ensure the library contains generator type G1.

Problem formation:

The three-bus system is given in Figure Q2. System voltage level is 400 kV. Voltages and line impedances are in per unit. The chosen system power base is 100 MVA.

Figure Q2

For transmission line, create a ‘line type’ for all three lines. For the ‘line type’:

•    Rated voltage: 400 kV

•    Rated current: 2 kA

•    Type: overheadline

•    1,2- Sequence reactance X’: 10 Ohm/km

•   Note: you need to go back to the line model to change the length of line to match the given impedance value in p.u.

For generator, select the provided generator type ‘G1’ in the library. However, change the generator ratings in the type to:

•    Rated apparent power: 200 MVA

•    Rated voltage: 400 kV

•    Rated power factor: 1.0

Question 2.1: Load Flow Result by Simulation [10 marks]

•    Run the power flow calculation

•    Record the solutions of active and reactive power flows on each branch as well as voltage magnitudes and phases of the buses. Analyse the results and present your  recordings in the form. of table in your report;   [10 marks]

Question 2.2: Verification of Simulation result by Hand Calculation using Newton-Raphson Approach [40 marks]

•    Write the bus admittance bus for this system                                 [5 marks]

•    Formulate the Newton-Raphson problem and formulate the Jacobian matrix with unknown quantities                           [5 marks]

•    With initial guess of θ2  = θ3  = 0°, |v3| =  1, find the values of Jacobian matrix elements and write the Jacobian matrix J0                      [5 marks]

•    Find the unknown quantities in the 1st  iteration, and compare with the exact results from the simulation                    [10 marks]

•    Continue to the 2nd  iteration, finding the updated Jacobian matrix J1  and calculate the unknown quantities in the 2nd  iteration, and compare with the exact results from the simulation and provide your remarks         

本研究基于扩展卡尔曼滤波(EKF)方法,构建了一套用于航天器姿态与轨道协同控制的仿真系统。该系统采用参数化编程设计,具备清晰的逻辑结构和详细的代码注释,便于用户根据具体需求调整参数。所提供的案例数据可直接在MATLAB环境中运行,无需额外预处理步骤,适用于计算机科学、电子信息工程及数学等相关专业学生的课程设计、综合实践或毕业课题。 在航天工程实践中,精确的姿态与轨道控制是保障深空探测、卫星组网及空间设施建设等任务成功实施的基础。扩展卡尔曼滤波作为一种适用于非线性动态系统的状态估计算法,能够有效处理系统模型中的不确定性与测量噪声,因此在航天器耦合控制领域具有重要应用价值。本研究实现的系统通过模块化设计,支持用户针对不同航天器平台或任务场景进行灵活配置,例如卫星轨道维持、飞行器交会对接或地外天体定点着陆等控制问题。 为提升系统的易用性与教学适用性,代码中关键算法步骤均附有说明性注释,有助于用户理解滤波器的初始化、状态预测、观测更新等核心流程。同时,系统兼容多个MATLAB版本(包括2014a、2019b及2024b),可适应不同的软件环境。通过实际操作该仿真系统,学生不仅能够深化对航天动力学与控制理论的认识,还可培养工程编程能力与实际问题分析技能,为后续从事相关技术研究或工程开发奠定基础。 资源来源于网络分享,仅用于学习交流使用,请勿用于商业,如有侵权请联系我删除!
评论
添加红包

请填写红包祝福语或标题

红包个数最小为10个

红包金额最低5元

当前余额3.43前往充值 >
需支付:10.00
成就一亿技术人!
领取后你会自动成为博主和红包主的粉丝 规则
hope_wisdom
发出的红包
实付
使用余额支付
点击重新获取
扫码支付
钱包余额 0

抵扣说明:

1.余额是钱包充值的虚拟货币,按照1:1的比例进行支付金额的抵扣。
2.余额无法直接购买下载,可以购买VIP、付费专栏及课程。

余额充值