利用BPA 计算短路点扫描:
<SHORT_CURRENT_SCAN_RESULT>
.# 母 线 故障类型 遮断电流 短路电流 短路容量 正序等值阻抗 负序等值阻抗 零序等值阻抗 分区
.# 1-单相/2-三相 (kA) (kA) (MVA) R1+jX1 (欧姆) R2+jX2 (欧姆) R0+jX0 (欧姆)
.#--------------------- --------------- -------- -------- --------- ------------------ ------------------ ----------------- ----
"BUS-39 " 100.0 B 0.0 2 200.000 109.663 18994.203 0.040 0.525 0.018 0.356 0.002 0.455 " 1"
"BUS-16 " 100.0 B 0.0 2 200.000 43.372 7512.175 0.413 1.266 0.310 1.146 1.886 7.930 " 1"
"BUS-2 " 100.0 B 0.0 2 200.000 42.039 7281.346 0.261 1.348 0.199 1.190 1.555 7.330 " 1"
"BUS-17 " 100.0 B 0.0 2 200.000 38.145 6606.992 0.416 1.455 0.320 1.353 1.846 7.677 " 1"
"BUS-3 " 100.0 B 0.0 2 200.000 38.058 6591.803 0.376 1.470 0.297 1.367 0.971 5.218 " 1"
"BUS-4 " 100.0 B 0.0 2 200.000 36.034 6241.281 0.416 1.547 0.332 1.441 0.003 0.463 " 1"
"BUS-6 " 100.0 B 0.0 2 200.000